Corona Loss
- When alternating voltage across transmission is raised beyond a certain level, the conductors are surrounded by pale violet glow and smell of ozone gas.
- It is called as Corona effect on the transmission line.
Critical disruptive voltage
- It is minimum phase to neutral voltage required to start ionization of air.
- Let us consider that distance between two conductors are d cm and its radii r cm.
- The potential gradient at the conductor surface is given by
g = V / [ r Loge ( d / r ) ]
V = go r Loge ( d / r )
- The effect of air density factor as well as surface of the conductor is considered for critical disruptive voltage.
VC = m0go δ r Loge
( d / r )
Where VC = Phase to neutral voltage
r
= Radius of conductor
d =
Diameter of conductor
g0
= Breakdown ( Dielectric ) strength of air at 76 cm of
mercury at 25
degree centigrade
= 30 kV / cm ( Max )
= 21.2 kV / cm ( RMS )
m0
= Irregular factor
= 1 for polished conductor
= 0.98 to
0.92 for dirty conductor
= 0.87 to
0.8 for stranded conductor
Air
density factor
- Under the standard condition of 76 cm of Hg and 25 degree centigrade, the air density factor is given by
- Air density factor δ = 3.92b / 273 + t
- Where b = atmospheric pressure of b cm
- The breakdown strength of air is directly proportional to air density factor. The air density factor under standard condition is taken as unity.
- Line voltage = √ 3 × VC
Visual critical voltage
- It is minimum phase to neutral voltage at which corona glow starts on the conductor. The visual critical voltage is higher than the disruptive critical voltage.
- VV = m0go δr { 1 + 0.3 / √ δr } Loge ( d / r )
Where
m0 = Irregular factor
g0 = Breakdown ( Dielectric ) strength of
air
r = Radius of
conductor
d = Diameter of
conductor
δ = Air density
factor
Power loss due to corona
- Under the normal weather condition, according to Peek’s Formula, The power loss due to corona is given by
- P = 242.2 [( f + 25 ) / δ ] √ r / d ( V – VC )2 × 10 – 5 kW / km / Phase
Where
f = Supply frequency
V = Phase to neutral voltage ( RMS )
VC = Critical disruptive voltage
( RMS ) per phase
δ = Air density factor
- Power loss due to corona α ( V – VC )2
- The power loss increases due to bad weather condition.
Advantages and Disadvantages of Corona Loss
Advantages
- It reduces transient produced by surges.
- Due to corona, virtual diameter of conductor increases which reduces electro – static stress between conductors.
Disadvantages
- Power loss
- It reduces the transmission line efficiency.
- Harmonic current
- Due to corona, non – sinusoidal current flows in the transmission line. It may cause inductive interference to nearby communication lines.
- Radio interference
Factors Affecting Corona Loss
Line voltage
- If the voltage is low, there is no change in surrounding condition of conductors.
- As voltage increases beyond certain limit, corona is formed due air around conductor becomes conducting.
Spacing between
conductors
- As the space between conductor increases, the electro-static stress on the conductor surface reduces which reduces effect of corona formation.
Diameter of
conductor
- The corona loss depends upon shape and size of conductor.
- It increases for rough and irregular surface of conductor as compared to polished surface.
- The stranded conductor has irregular surface as compared to solid conductor, therefore corona loss reduces on the stranded conductor.
Atmosphere
condition
- The corona is formed due to ionization of air surrounding conductor.
- The number of ions more in the stormy weather, therefore corona occurs at much less voltage as compared to standard weather condition.
Methods of Reducing Corona Loss
- Increasing space between conductors
- Increasing diameter of conductor : Large diameter, Hollow conductor and Bundle Conductors.
You may also like to read this articles
: Construction
and working of earthing transformer Construction
and working of hysteresis motor Compare
distribution transformer and power transformer |
Corona loss in HVDC Transmission lines
- The negative charged particle near the conductor surface moves from negative conductor to positive conductor continuously.
- There is a electric field distribution between positive conductor and negative conductor.
- The corona loss in the HVDC transmission line is less due to √ 2 factor ( Maximum voltage in the ac transmission line = √ 2 × RMS ac voltage ) in the voltage waveform.
- The corona loss in the DC transmission line does not affect as much as that of AC transmission line in the bad weather condition.
- The corona loss is minimum in the monopole lines.
No comments:
Post a Comment