In this article, drying of switchgear is given by the
Megger. The switchgear equipment is dried out before used in the system.
Insulation Resistance
- A 1000 V megger is used for measurement of insulation resistance, for higher rating motorized megger of 2.5 kV shall be used.
- The switchgear equipment first dried out before it is switched when
Insulation Resistance of switchgear
Insulation Resistance |
Voltage Rating |
< 1 Mega ohm |
Rated 1000 V |
100 Mega ohm |
Rated voltage
above 1000 V and up to including 33 kV |
1000 Mega ohm |
Rated voltage
above 33 kV |
Drying out of switchgear
- It is noted that continuously apply heat for a considerable time so as to dry out moisture.
- It is recommended to takes insulation resistance periodically during drying out period.
- It is generally found that at the beginning of drying out, moisture is redistributed.
- The value of insulation resistance becomes minimum after some time and stability this value for some time, after that its value increases and reaches its maximum value.
- This value is generally much greater than value specified in above table.
- The switchgear equipment is safer to put into service when the insulation resistance has been reached.