There are following types of distribution system.
Radial distribution system
- Figure shows radial distribution system. One feeder PQ is radiate out from the substation.
- It feeds distributor from one end only.
- The distributor is fed at point A and terminates at point D.
- It means that the load is given at first consumer A and last consumer D.
- Obviously, the last consumer gets less voltage due to voltage drop in the distributor.
Advantages
- Simple distribution system
- Less initial cost
Disadvantages
- When a fault occurs on distributor, power supply is completely interrupted at fault point to all the consumers
- Consumer at far end gets reduced voltage
- If the distributor is extended for future load, the voltage drops increase
Ring distribution system
- It is a distributor in the closed loop and fed at one or more point.
- Such a distributor starts from one point and makes loop through area and finally returns to the same point.
- The distributor can be considered as series of open distributors fed at both ends.
- The ring distributor feeding from one point is shown in the figure.
- Here P is feeding point and PQRSTUVWP forms closed loop for feeder. The tapings for the distributor is taken from point R, T and V respectively.
- The distributors A, B and C are shown in the figure.
- It is equivalent to straight distributor fed at both ends with equal voltage for the calculation purpose.
Advantages
- Less copper requires than the radial system
- Less fluctuation of voltage at consumer’s end
- Reliability increases, if the fault occurs at point, the power supply are maintained from other point.
Interconnected distribution system
- When the ring feeder is energized through two or more than two generators / substations, it is called as interconnected system.
- Figure shows two substations S1 and S2 which feeds feeder PQRSTUVWP.
- If there is fault between feeders RS, the feeder Q and R receives power through substation S1 and feeder S receiver power through substation S2.
Advantages
- Service reliability increases
- Good voltage regulation is achievable
- Peak load can be fed from the other substation and this will reduces the reserve generating capacity
You may also like :
Compare – Audio Amplifier & Tuned Amplifier
Compare – Intrinsic Semiconductor & Extrinsic
Semiconductor
Compare – SCR & Asymmetrical SCR
No comments:
Post a Comment