- The power factor compensation can be provided either LT or HT side of the distribution transformer.
- The electricity board measured power factor at the HT side for penalty calculation.
- The power factor compensation provided by the HT capacitors and LT capacitors.
- We will discuss the advantages and disadvantages of LT capacitors over HT capacitors.
Let us consider two cases in which capacitor are connected at the HT side and LT side.
Capacitor connected to HT side
- When a capacitor connected to HT side of transformer, the reactive power of capacitor does not flow through transformer.
- This will does not affect the power factor of LT side.
Capacitor connected to LT side
- When a capacitor connected to LT side of transformer, the reactive power flows through the transformer and therefore the power factor improves.
- This will result in reduced current flows through HT side as well as LT side.
Consider a 1000 kVA transformer in
which full load copper losses are 10 kW.
When 500 kW load is connected to the secondary side. Calculate power
saving when capacitor is connected at the LT side. Consider that the energy
charges is Rs. 6 per kWh and power factor of transformer is 0.8 lagging
Solution
When capacitor is connected at HT side
The operating power factor of the transformer say Cos Φ1 = 0.8
When capacitor is connected at LT side
The operating power factor of the transformer say Cos Φ2 = 0.98
K = Load in kW / kVA rating of transformer
= 500 / 1000
= 0.5
Power saving
= Wcu × K × ( 1 / Cos Φ1 – 1 / Cos Φ2 )
= 10,000 × 0.5 × ( 1/ 0.8 –
1/0.98 )
= 10,000 × 0.5 × ( 1.25 – 1.020
)
= 10,000 × 0.5 × ( 0.23 )
= 1150
watt
Monthly saving
= 1150 × 24 × 30 /1000 = 828 kW
Let us consider
that the energy charges is Rs. 6 per kWh
Monthly saving
= Rs 6 × 828 = Rs. 4968
Yearly saving =
Rs.4968 × 12 = Rs.59616
Transformer
Capacity
- When capacitor is connected to HT side, the maximum load that can be connected to transformer is 1000 kVA × 0.8 = 800 kW
- When capacitor is connected to LT side, the maximum load that can be connected to transformer is 1000 kVA × 0.98 = 980 kW
Advantages
of capacitor connected at LT side
- The cost of LT capacitor is less as compared to HT capacitors
- Maintenance of LT capacitor panel is easier as compared to HT capacitors