Significance
The short circuit on the single phase transformer is performed in order to find out
equivalent circuit parameters of the transformer. This test is performed to
find out
- Copper losses at full load as well as any load
- Equivalent impedance as referred to primary (Z01) or secondary side (Z02)
- Equivalent leakage reactance as referred to primary (X01) or secondary side (X02)
- Equivalent resistance as referred to primary (R01) or secondary side (R02)
- Voltage drop as referred to primary or secondary side
- Voltage regulation at any load and power factor
- Voltage transformation ratio
Instruments required
Instrument |
Specification |
AC
voltmeter |
|
AC
ammeter |
|
Wattmeter |
|
Multi
meter |
|
Single
phase auto transformer |
|
- In this test, the low voltage winding is usually short circuited by thick wire or ammeter and supply is given to the high voltage winding.
- The supply to the high voltage winding is given by using auto transformer.
- The applied voltage Vsc is gradually increases till the ammeter shows the full load current.
- As the applied voltage Vsc is very low ( only 5 – 10% of the normal voltage ), core flux is very small, iron losses are small so it is neglected.
- The wattmeter Wsc shows full load copper losses of the transformer.
- Full load copper losses of both winding Wsc = Isc2 R01
⸫
R01 = Wsc / Isc2
- Equivalent impedance as referred to primary side
Zsc
= Z01 = Vsc / Isc
⸫
X01 = √ ( Z012
– R012 )
- The voltage transformation ratio ( k ) can easily find out by taking reading of HV winding and LV winding.
- The transformer equivalent circuit parameter can easily determined as referred to secondary side after calculating voltage transformation ratio ( k ).
R02
= R01 / k2
X02
= X01 / k2
Z02
= Z01 / k2
Circuit
diagram
Procedure
- Make connection as per circuit diagram
- Keep the voltage of the auto transformer with zero voltage position
- Switch on the supply and slowly increase the auto transformer voltage until the ammeter shows the full load current
- Note down the reading of ammeter, voltmeter and wattmeter.
Precaution
- It should be kept in mind that setting of the auto transformer must be in minimum or zero voltage position before switch on the supply.
Observation
table
Short
circuit voltage |
Short
circuit current |
Short
circuit power |
Vsc |
Isc |
Wsc |
|
|
|
Calculation
Short circuit input
Power |
Wsc = Vsc
Isc Cos Φsc |
Short circuit power
factor & power factor
angle |
Cos Φsc =
Wsc / Vsc Isc
Φsc = Cos
– 1( Wsc / Vsc Isc ) |
Transformer winding resistance
as referred to primary side |
R01 = Wsc
/ Isc2 |
Transformer winding impedance
as referred to primary side |
Vsc
/ Isc |
Transformer winding reactance
as referred to primary side |
X01
= √ ( Z012 – R012 ) |
Voltage
transformation ratio ( k ) |
k = I1 / I2
= Isc / I2 |
Transformer winding resistance
as referred to secondary side |
R02
= R01 / k2 |
Transformer winding impedance
as referred to secondary side |
Z02
= Z01 / k2 |
Transformer winding reactance
as referred to secondary side |
X02
= X01 / k2 |
Full load copper
losses |
Isc2
R01 |
Voltage drop as
referred to primary side |
Isc
( R01 + j X01 ) |
Voltage drop as
referred to secondary side |
I2
( R02 + j X02 ) |
Voltage regulation at
any load and any power factor + sign for lagging
power factor – sign for leading
power factor 0V2
= No load voltage |
I1
R01 Cos Ф2 ± I1 X01 Sin Ф2
/ ( 0V2 ) OR I2
R02 Cos Ф2 ± I2 X02 Sin Ф2
/ ( 0V2 ) |
- The wattmeter shows full load copper losses and iron losses of the transformer.
- As the supply voltage is only small amount of rated voltage, iron losses is neglected therefore the wattmeter shows full load copper losses.
Which
winding of the transformer is short circuited? LV winding or HV winding. Give
reason
- The LV winding of the transformer is short circuited.
- Let us try to understand reason for that, consider a 10 kVA, 1100 V / 220 V transformer, if supply is given to LV side, voltage required for full load current flows through winding during short circuit of HV winding lies between 5% to 10% of rated value i.e ( 220 × 5 ) / 100 = 11 V to ( 220 × 10 ) / 100 = 22 V which is very small.
- At low voltage ( 11 V to 22 V ), high precision reading would not be obtained by ordinary meter.
You
may also like :
Standard kVA rating of three phase transformer
Technical
specification of three phase transformer
No comments:
Post a Comment