- The main function of the booster transformer is to compensate voltage drop in the feeder when feeder is very far away from it.
- The secondary winding of the booster transformer is connected in series with the line whereas the primary winding of the booster transformer is supplied through secondary of the regulating transformer.
- The secondary winding of the regulating transformer is adjusted such that the booster transformer secondary voltage is in phase with the feeder voltage.
Voltage V1 + Booster voltage = Voltage V2
- The magnitude of the feeder voltage can be regulated by adjusting tapping on the secondary side of the regulating transformer.
- The rating of the booster transformer is only fraction to that of main transformer.
Rating of single phase booster transformer
= ( Line current × Boost voltage / 1000 ) kVA
Rating of three phase booster transformer
= ( √3 × Line current × Boost voltage / 1000 ) kV